UNIT DOWN? Verified OEM & Aftermarket Fix Kit Below
Jump to Parts Kit ↓
HARDWARE SYMPTOM MODEL: T-49F-HC

True T-49F-HC: Warm Cabinet / Continuous Run

Observed Condition: Cabinet rises above -10°F; compressor runs hot or cycles on thermal overload.

Immediate Non-Invasive Triage: Inspect condenser coil behind front louver; verify condenser fan rotation; check suction/head pressures if coil is clean.

Platform Cross-Reference: True's 7-7-7 Hydrocarbon warranty, reversing condenser fan motor (RCU) dust-clearing cycle, and T-Series installation/electrical compliance rules apply across the True T-Series -HC family.

Verified Replacement Parts & Fix Kit

RoleOEM MPN / SpecComponent & Fitment NotesEst. StreetCheck Stock
Part 1
oem replacement part
945035 Evaporator Fan Blade (115V)
Confirm rotation & diameter via serial number.
OEM ~$25–$55
Part 2
oem replacement part
960276 Condenser Fan Blade
Match to OEM specification.
OEM ~$30–$60
Part 3
oem replacement part
983911 Hermetic R290 Compressor
Always verify exact 115V/60Hz R290 compressor P/N by True serial number. Required for warranty/A3 compliance.
OEM ~$650–$1,100
Part 4
oem replacement part
851111 Capillary Tube (R290)
Match exact ID/length to unit serial PCN. Requires EPA-certified R290 technician.
OEM ~$79 / Generic ~$15–$25
Replace Unit DROP-IN SPEC Repair Exceeds Appliance Value?
Compare verified commercial reach in foodservice freezer nsf 7 replacements & cutout specs.
Compare See Top Replacements →

Failure Physics & Technician Isolation

Safety & Disassembly Warnings:
  • Servicing the R290 hydrocarbon sealed refrigeration system requires EPA-certified hydrocarbon technicians, spark-free recovery/evacuation equipment, nitrogen purging, and simultaneous filter drier + capillary tube inspection/replacement to prevent oil-coking restrictions.
  • Do not attempt to disassemble foamed-in-place cabinet insulation or buried rear drain-line chases without destructive intervention.

Root Mechanism: Condenser Coil Fouling -> Compressor Overheat

Trigger: Normal operation in commercial kitchen environment

Physics / Degradation: Floor-level lint/grease coats condenser fins, reducing heat rejection. This leads to elevated head pressure and discharge temperature.

System Lockout / Impact: Compressor cycles on thermal overload, leading to reduced cooling performance, increased energy consumption, and eventually oil coking or winding failure of the compressor.

Root Mechanism: Capillary Tube Restriction / Oil Coking

Trigger: Compressor overheat or moisture/debris ingress after prior sealed-system service.

Physics / Degradation: Wax, carbon, or other contaminants (oil coking) plug the first 1–2" of the small ID capillary tube, or the filter drier becomes restricted.

System Lockout / Impact: Starved evaporator, resulting in low suction pressure, poor cooling performance, and a warm cabinet. Can lead to eventual compressor failure.

Before Ordering Parts: Normal Behavior vs. True Fault

False-Alarm Check — Temporary cabinet air temp rise during scheduled defrost; evaporator fan stops briefly.: This is a normal time-initiated, temperature-terminated automatic defrost cycle designed to melt frost from the evaporator coil. (True fault when: If the cabinet does not return to -10°F within 30–45 minutes after defrost termination, or if the evaporator fan does not restart.)
False-Alarm Check — Evaporator fan stops immediately when either door opens.: The door switch intentionally cuts the evaporator fan to prevent warm, humid air from being drawn across the cold evaporator coil, reducing frost buildup and energy consumption. (True fault when: If the evaporator fan does not restart when the door is closed (or door switch is manually depressed).)

Other True T-49F-HC Fault Signals