Meross EM16: Negative Power / Sales Volume Reading
What this means: App displays negative Watts or negative solar export for a circuit that should be consuming or exporting positively.
60-Second Verification Check
Verify CT is on the phase matching its jack bank (A1–A6 -> La, B1–B6 -> Lb, C1–C6 -> Lc), or invert CT polarity in app.
Verified Replacement Parts
60A Branch Split-Core CT (2.5mm jack)
Requires matching OEM specifications for accuracy and safety.
200A Main Split-Core CT (3.5mm jack)
Requires matching OEM specifications for accuracy and safety.
Why This Happens & Safety Warnings
- "Do not perform any maintenance, service, or cleaning of the EM16P after installation." (``)
- "Do not open, disassemble, or attempt to repair the device." (``)
What triggers it: Incorrect installation of branch CTs relative to the voltage reference phases (La, Lb, Lc).
What wears out inside: Clamping a CT from one phase bank (e.g., C-bank) onto a circuit breaker on a different physical phase (e.g., Phase A) than its voltage reference (Lc), leading to a 180° phase error in power calculations.
Symptom on machine: Inaccurate or negative Watt/Power Factor readings for affected circuits, leading to incorrect energy monitoring and automation.