WattCycle FS-351: Discharge OCP Alarm / Sudden AC Loss
What this means: BMS detects discharge current exceeding 120A +/- 10A for 10 seconds, or 125A air circuit breaker trips.
60-Second Verification Check
Check battery touchscreen LCD for 'Discharge OCP' alarm. Verify AC load on inverter. Reset 125A air circuit breaker.
Verified Replacement Parts
Front-Panel 125A DC Air Circuit Breaker
Must match physical cutout, voltage, and current rating for DC applications.
Why This Happens & Safety Warnings
- WattCycle's official warranty policy explicitly notes that opening the battery for inspection at the direction or authorization of WattCycle Support does not void warranty coverage. This implies that unauthorized opening without explicit instruction may void the warranty.
- The inverter contains high-voltage components (up to 300Vdc+ PV/bus) and should only be serviced by qualified personnel.
What triggers it: Operating 6.5kW inverter with a single 48V 100Ah battery.
What wears out inside: Inverter attempts to draw 120A-150A DC, exceeding the battery's 100A continuous discharge rating and 120A OCP threshold.
Symptom on machine: Sudden AC power loss from inverter, requiring manual reset of the 125A air circuit breaker. System cannot deliver full advertised inverter power.
Cross-Compatible Platforms: 5+2 year US warranty policy (requires 3-month online registration), 6,000+ cycle life at 80% DoD, and CAN/RS485 inverter protocol library (Victron, Deye, Growatt, GoodWe, SOFAR, SMA, Pylontech).