Observed Condition: Display or app reports sensor open/short fault; heating output shuts off. E1 for internal sensor, E2 for external sensor.
Immediate Non-Invasive Triage: If E2 occurs when using air-only heating (no floor probe wired), change the Sensor Mode in settings from 'Both'/'External' to 'Internal Only'. If a floor probe is wired, measure resistance with a multimeter (~10 kOhm @ 25°C).
Platform Cross-Reference: Shares the Meross Matter-over-Wi-Fi 2.4 GHz provisioning stack and tempered glass capacitive touch UI with the MTS200MA / MTS200HK / MTS200B series.
| Role | OEM MPN / Spec | Component & Fitment Notes | Est. Street | Check Stock |
|---|---|---|---|---|
| Part 1 routine consumable |
Included 3m NTC Sens | External Floor Temperature Sensor Probe Direct drop-in match for resistance-temperature curve and physical form factor. |
$6 – $12 (Generic) | |
| Replace Unit | DROP-IN SPEC | Repair Exceeds Appliance Value? Compare verified hvac smart thermostats zone controllers replacements & cutout specs. |
Compare | See Top Replacements → |
Trigger: Reusing an existing buried floor sensor from a legacy thermostat
Physics / Degradation: The existing probe has a different resistance-temperature curve (e.g., 12kOhm, 15kOhm, or 47kOhm) than the MTS200's required 10kOhm B=3950 specification.
System Lockout / Impact: Inaccurate floor temperature readings, incorrect heating control, or the thermostat triggering an 'E2' sensor fault and shutting off heating.