Symptom Guide Model: IS335

Honeywell IS335: Continuous Flashing Red LED with Alarm Relay Latched Open (Supervisory Trouble State)

What this means: Indicates either normal initial power-up warm-up (<45 seconds) OR a latched supervisory self-test failure caused by DC supply voltage dropping below 9.0 VDC, a failed dual-element pyroelectric sensor, or a fault in the dual-slope temperature compensation circuit.

1

60-Second Verification Check

⚠ Quick Check Before Buying Parts: Red status LED flashes slowly and the detector does not immediately report normal standby upon applying 12 VDC power. — The IS335 requires up to 45 seconds of initialization warm-up time from initial power application for internal analog amplifiers and dual-slope references to stabilize, during which the red LED flashes slowly by design.

Wait at least 45 seconds after initial power application to rule out normal warm-up. If flashing and open zone fault persist, measure DC voltage across V+ and V- terminals with a multimeter to verify supply is between 9.5 VDC and 15.0 VDC (minimum 9.0 VDC), power-cycle the detector, and conduct a walk test. If voltage is within spec and the fault does not clear after power-cycling, the manual directs replacing the entire sensor assembly.

Target: 9.0 VDCTarget: 9.5 VDCTarget: 15.0 VDC
2

Verified Replacement Parts

#1 Most Likely Fix ~$0.15/ft

4-Conductor Low-Voltage Intrusion Alarm Cable

4-conductor 22 AWG to… Copy Part #

Matches the 6-position terminal block clamping capacity (22 to 20 AWG) and official Honeywell cable specifications.

Repair Cost Too Close to a New Unit? Compare top-rated drop-in security replacements & dimensions.
Compare Replacements →
Why This Happens & Safety Warnings
Safety & Disassembly Notes:
  • Verify input voltage (>= 9.0 VDC nominal; >= 9.5 VDC for UL 639 Listed installations), power-cycle the detector, and perform a walk test if a supervisory trouble condition (flashing red LED and open relay) occurs; if trouble does not clear, replace the entire sensor.
  • Never connect AC mains or non-power-limited line voltage directly to the 9.0-15.0 VDC Class 2 power-limited input terminals.
Supervisory Self-Test Lockout on Auxiliary DC Supply Voltage Sag (<9.0 VDC)

What triggers it: Host control panel auxiliary 12 VDC rail drops below 9.0 VDC (or below 9.5 VDC UL threshold) due to AC utility outage with aging panel standby battery, overloaded auxiliary power bus (>600 mA on legacy panels), or excessive voltage drop over long 22 AWG wire runs.

What wears out inside: Undervoltage on the internal DC regulation stage causes the continuous supervisory self-test routine to fail, intentionally de-energizing and latching open the Form A solid-state relay while flashing the red status LED.

Symptom on machine: Continuous zone fault / trouble condition on the alarm control panel that prevents arming or triggers a false alarm until supply voltage is restored above 9.5 VDC and the sensor is power-cycled and walk-tested.

Internal Pyroelectric / Comparator Failure or ESD Puncture During Installation

What triggers it: Ungrounded technician touches exposed PCB traces/components while removing the circuit board for wiring, or an internal electronic component fails during service life.

What wears out inside: Electrostatic discharge punctures the high-impedance FET gate inside the pyroelectric sensor or CMOS dual-slope comparator, or random electronic degradation causes the onboard supervisory self-test check to fail despite valid 9.5-15.0 VDC supply power.

Symptom on machine: Sensor becomes permanently unresponsive or latches into permanent supervisory trouble (flashing red LED and open alarm relay), requiring complete unit replacement.

Cross-Compatible Platforms: Direct form-fit-function replacement for discontinued Ademco/Honeywell Aurora wired motion detectors

Other Honeywell IS335 Problems (3)
1. Quick Test 2. See Fix Parts ↓